Chapter 3: Accessing the ACS 6000 Console Server via the Web Manager 37
5. Click Save.
Table 3.7: Power Parameters
Parameter Description
Physical
Enable Cisco RJ-45
Pin-Out
Defines the serial port pinout. Default setting: Disabled.
Status Defines the status of the serial port as either enabled or disabled.
Default: Disabled.
Speed Defines the speed as 300, 1200, 2400, 4800, 9600, 19200, 38400,
57600 or 115200. Default: 9600.
Parity Defines the parity as either Even, Odd or None. Default: None.
Data Bits Defines the data bits as either 5, 6, 7 or 8. Default: 8.
Stop Bits Defines the stop bits as either 1 or 2. Default: 1.
Flow Control Defines the flow control as none, hardware, software, RxON software
or TxON sofware. Default: None.
Power
PDU Type Defines the type or vendor of the PDU connected to the serial port.
Auto - the vendor will be detected.
Avocent-Cyclades - Avocent-Cyclades PM PDU family.
SPC - SPC power control device family.
Server Tech - Server Tech family.
Default: Auto.
Enable Speed Auto
Detection
When enabled, detects the speed of the port. Default: Disabled.
Pooling Rate The interval in seconds to update information from the PDU. Default:
20.
For Avocent/Cyclades
PDUs
Power Cycle Interval The interval in seconds between Off and On actions for the power
cycle command. Default: 15.
Syslog When enabled, the PDU will send syslog messages to the appliance.
Default: Enabled.
Buzzer Enables or disables the PDU’s buzzer. Default: Enabled.
SW Overcurrent
Protection
When enabled, the software’s overcurrent protection is on. Default:
Disabled.